100% direct-to-chip liquid
Warm-water supply up to 45 °C to fanless rack-scale systems. No air plant in the IT modules. Adiabatic dry coolers (N+1) handle most hours; a trim chiller covers extreme ambient.
Product · Data Cell
Compute follows power. The GridCell Data Cell is a 5 MW IT cell designed for NVIDIA Vera Rubin-class rack-scale systems: 16 compute and 6 network/storage positions at a 330 kW-per-position design basis, 100% direct-to-chip liquid cooling, and dedicated space for CDUs, manifolds, leak detection, and clean-agent fire protection. It arrives as about 14 factory-built modules. Campuses scale as multiples of 5 MW.
Standard SKU · 5 MW Data Cell · Vera Rubin-class design basis
Stamp framing
A 5 MW cell of 330 kW racks does not fit in one shipping container. The Data Cell is a matched set of factory-built modules, most of them wider and taller than a standard ISO box, shipped as oversize permit loads and set on one pad. The buyable catalog is 5 MW only; scale-out is additive (10 / 15 / 20 MW…).
16 compute positions at ~330 kW plus 6 network/storage positions, capped at 5.0 MW IT. Two wide IT modules each hold 8 compute + 3 network positions.
2 wide IT modules (~14 ft W × 45–50 ft L × 11–12 ft clear) · 1 CDU/pump module · 2 electrical modules · 1 network/MMR module · ~8 heat-rejection skids (7 dry coolers N+1 + 1 trim chiller).
Campuses grow by count, not alternate SKUs. Interim smaller capacity is discussed project-by-project—still mapped to the 5 MW grammar.
Inside the Data Cell
The cell provides the infrastructure: power, cooling, space, and safety. Tenants bring their own rack-scale compute, which is installed on site into a ready 5 MW cell.
Warm-water supply up to 45 °C to fanless rack-scale systems. No air plant in the IT modules. Adiabatic dry coolers (N+1) handle most hours; a trim chiller covers extreme ambient.
A dedicated CDU/pump module (N+1 CDUs), with filtration, expansion, and make-up. Each IT module has counted space for row manifolds, branch valves, and drip containment.
8 contiguous compute positions per IT module for rack-scale domains, A/B busway sized for 330 kW positions, overhead fiber paths, and a steel deck rated for heavy liquid-cooled racks.
Clean-agent total-flooding suppression and VESDA aspirating smoke detection in each IT module, with dedicated cylinder space. Zoned leak detection isolates a rack or row branch without shutting the cell down.
| Catalog rating | 5 MW Data Cell — capped at 5.0 MW IT; designed for NVIDIA Vera Rubin-class rack-scale systems (Vera Rubin NVL72 class) |
|---|---|
| Rack power basis | ~330 kW per compute position (design basis; matches N+1 rack power-shelf capacity, with headroom above published rack TDP) |
| Rack positions | 16 compute + 6 network / storage positions (22), capped at 5.0 MW IT. 8 compute + 3 network per IT module |
| Cooling | 100% direct-to-chip liquid; warm-water supply up to 45 °C; CDUs N+1; 7 adiabatic dry coolers (N+1) + 1 trim chiller |
| Liquid (indicative) | ~500 L/min (~130 GPM) per 330 kW position at ΔT ≈ 10 K (calculated; confirmed per rack OEM) |
| Electrical | 2 electrical (LV power block) modules; 415/480 VAC A/B busway to each IT module; UPS for CDUs, network, and controls; reserved 800 VDC path |
| IT modules | 2 wide prefab modules, ~14 ft W × 45–50 ft L × 11–12 ft clear; steel deck ≥30 kPa in rack zones; racks installed on site |
| Module set | ~14 shipping modules (range 12–17): 2 IT · 1 CDU/pump · 2 electrical · 1 network/MMR · ~8 heat-rejection skids. Oversize permit loads, not standard ISO containers |
| Safety | Clean-agent suppression + VESDA smoke detection per IT module (dedicated cylinder space); zoned leak detection with branch isolation |
| Power interface | Fed from matched ~6 MW firm Power Cell (gas or power-ready) via standardized MV/LV interface |
| Scale-out | Multiples of 5 MW by adding Data Cells (and matched Power Cells) |
Next-gen option Provisional
For the next Rubin Ultra-class generation, the same 5 MW cell is planned around 8 compute racks at ~600 kW, each with an 800 VDC power sidecar, plus 4 network positions, still capped at 5.0 MW IT. Total heat and power are the same, so the cell stays at about 14 modules (range 12–18). The base cell can be built next-gen ready (pair layout, larger headers, heavier deck, 800 VDC bay). All next-gen values are provisional until the platform is published and confirmed.
On the pad
Data Cells land beside Power Cells so AI stamps are not waiting on distant interconnection alone. Add cells as tenant demand grows—same interfaces, same pad grammar.
We name the hardware class the cell is designed for (NVIDIA Vera Rubin-class rack-scale systems) as a design basis only. It does not imply a partnership or certification, and tenant names stay off this site.
Matched Power Cells deliver ~6 MW firm for each 5 MW Data Cell. With warm-water liquid cooling, peak facility overhead is ~7–16%, so 6 MW holds with margin.